Variable frequency drive Salicru CV50, high-performance multifunction vector drive for pumps, fans and machinery. Three-phase motors of up to 500 kW (670 HP) at 400 V.
By card (Redsys), bank transfer or PayPal (surcharge applies)
Technical advice: +34 694 203 910
The CV50-5000-4F (Salicru code 6B1CA000028) is a variable frequency drive —also called a frequency converter— of the series Salicru CV50, high-performance multifunction vector drive. It is supplied at 400 V three-phase. Controls asynchronous motors of up to 500 kW (670 HP) with an output current of 860 A in constant torque.
💧 Drive for pumpsPressure booster sets, irrigation pumps, transfer and circulation with PID control. | 🌬️ Drive for fansExtractor fans, industrial ventilation and air conditioning with energy saving. | 🏭 MachineryConveyor belts, mixers, kneaders and general-purpose machines. |
| Model | CV50-5000-4F |
| Salicru code | 6B1CA000028 |
| EAN | 8436035922505 |
| Series | Salicru CV50 |
| Motor power | 500 kW (670 HP) |
| Output current | 860 A (constant torque) |
| INPUT | |
| Rated voltage | Three-phase 380 V (-15%) ÷ 440 V (+10%) |
| Rated frequency | 50/60 Hz Permitted range: 47 ÷ 63 Hz |
| OUTPUT | |
| Rated voltage | Three-phase, 0 ÷ 100% of the input voltage |
| Frequency | 0 ÷ 400 Hz |
| Permissible overload | Constant torque: 150% for 1 min; 180% for 10 s; 200% for 1 s Variable torque: 120% for 1 min |
| Maximum distance | <50 m without filter / between 50 and 100 m install ferrites / >100 m LC filter |
| CONTROL SPECIFICATIONS | |
| Motor type | Asynchronous |
| Control method | V/f, Sensorless Vector Control, Torque control |
| V/f characteristics | Linear, quadratic (3 types), user-defined |
| Control resolution | 1% of the maximum output frequency |
| Speed fluctuation | ±0.3% (in vector control mode) |
| Braking unit | Integrated for ≤30 kW, external (optional) for ≥37 kW |
| INPUT SIGNALS | |
| Digital | 8 programmable inputs, PNP or NPN logic, pulse input, maximum frequency 50 kHz, selectable polarity, virtual activation, On/Off delay times |
| Analogue | 2 inputs, AI2: 0 ÷ 10 V / 0 ÷ 20 mA and AI3: -10 ÷ 10V Integrated potentiometer |
| OUTPUT SIGNALS | |
| Relay | 2 multifunction changeover NO/NC outputs Maximum 3 A / 250 V AC, 1 A / 30 V DC. Selectable polarity and on/off delay |
| Power supply | 24 V (±10%) 200 mA |
| Analogue | 2 selectable outputs 0 ÷ 10 V / 0 ÷ 20 mA, proportional to frequency, current, speed, voltage, torque, etc. |
| Digital | 1 multifunction open collector output (200 mA / 30 V) 1 output selectable between pulses (max. 50 kHz) and open collector Selectable polarity and on/off delay |
| Communication port | RS-485 Modbus-RTU |
| OPERATION | |
| Method | Console, control terminal block and communication. Removable console up to 200 m for models ≥ 18.5 kW. For the other models, remote console (up to 200 m) as an accessory. |
| Frequency setting | Digital, analogue, pulse train, multi-step, simple PLC, PID, Modbus communication |
| Protections | Overcurrent, overvoltage, undervoltage, drive overheating, phase loss, overload, underload, etc. |
| FILTERING | |
| EMC filter | Integrated. Category C3 |
| DC choke | Allows installation on drives ≥37 kW |
| GENERAL | |
| Ambient temperature | -10° ÷ 50°C (derating of 3% per degree above 40° C) |
| Degree of protection | IP20 |
| Cooling | Via easy-maintenance fans |
| Installation | Cabinet back-plate mounting, flange type and floor-standing for ≥ 220 kW |
| STANDARDS | |
| Safety | EN 61800-5-1 |
| Electromagnetic compatibility (EMC) | EN 61800-3 C3 |
| OTHER | |
| Keypad | Removable, included |
| DIMENSIONS AND WEIGHT | |
| Dimensions (H × W × D) | 1700 × 620 × 560 mm |
| Net weight | 450 kg |
What motor can I connect to the CV50-5000-4F?
Three-phase asynchronous motors of 400 V up to 500 kW (670 HP) and 860 A. With a 230/400 V motor, connect it in star (Y); with a 400/690 V motor, in delta (Δ).
Can I use it with a single-phase supply?
No. This model requires a three-phase 380-440 V supply. For a single-phase supply there are the CV10 and CV30 with 230 V single-phase supply.
Data sheet
Specific References
Official manufacturer documentation. It opens on their website, always the latest version.
Brand: SALICRU
Manufacturer: Salicru S.A.
Address: Avda. de la Serra, 100
Postal Code: 08460
City: Santa Maria de Palautordera
Country: Spain
Phone: +34938482400
Other: Contacto electrónico: salicru@salicru.com - https://www.salicru.com/contacto.html
Your review appreciation cannot be sent
Report comment
Report sent
Your report cannot be sent
Write your review
Review sent
Your review cannot be sent
Reference: 6B1CA000025
Brand: SALICRU
Reference: 6B1CA000020
Brand: SALICRU
Reference: 6B1CA000011
Brand: SALICRU
Reference: 6B1CA000007
Brand: SALICRU
Salicru floor-mounting installation base for CV50
Salicru side cover for harsh environments for CV30, CV50
Salicru side cover for harsh environments for CV50
Salicru side cover for harsh environments for CV30
Variable frequency drive Salicru CV50, high-performance multifunction vector drive for pumps, fans and machinery. Three-phase motors of up to 500 kW (670 HP) at 400 V.
check_circle
check_circle