All the alarm codes that Osaka F-1 / F-10 / F-30 can show (models: F-1, F-10, F-30, Pack F-10 + F-30), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.

Search all families · Is it a drive or a soft starter? Drive and soft starter fault codes

Important: this information is for guidance only and comes from each manufacturer's manual; your particular unit may behave differently, so always check the manual for your exact model. Any inspection or repair must be carried out by a qualified professional. Electrosuministros.es accepts no liability for how it is used.

All alarm codes of Osaka F-1 / F-10 / F-30

Models: F-1, F-10, F-30, Pack F-10 + F-30. Official source: Manufacturer manual (osakasolutions.com)

CodeMeaningLikely causeWhat to check
E1 / -E1
Probe
Probe Pr1 error (E: probe open; -E: short-circuited). Probe disconnected, short-circuited or out of range, or cable damaged. Check the configured probe type and the wiring, and measure the probe; replace it if damaged.
E2 / -E2
Probe
Probe Pr2 error (E: probe open; -E: short-circuited). Probe disconnected, short-circuited or out of range, or cable damaged. Check the configured probe type and the wiring, and measure the probe; replace it if damaged.
E3 / -E3
Probe
Probe Pr3 error (E: probe open; -E: short-circuited). Probe disconnected, short-circuited or out of range, or cable damaged. Check the configured probe type and the wiring, and measure the probe; replace it if damaged.
EPr
Memory / internal data
Possible EEPROM memory fault. Internal error in the parameter memory. Press the SET key or switch the unit off and on; if it persists, replace the controller.
Err
Memory / internal data · Locks the unit
Serious memory error (irreversible). Fatal failure of the controller memory. Replace the controller or send it for repair.
od
Other
Start-up delay after power-on in progress. This is the normal delay after switching on the power. Not a fault: wait for it to finish.
Ln
Other
Keypad locked. The keypad is locked by a parameter or automatically. Unlock the keypad as described in the manual.
Hi
High temperature
Maximum temperature alarm in progress. The temperature exceeds the programmed maximum limit. Check the door, defrost, thermal load and the A.HA limit.
Lo
Low temperature
Minimum temperature alarm in progress. The temperature is below the programmed minimum limit. Check the setpoint, the compressor contact and the A.LA limit.
AL
Other
Digital input alarm in progress. The digital input configured as an external alarm has been activated. Check the external equipment and the input configuration (i.Fi).
oP
Door
Door open alarm. The door input has been active for longer than the configured time. Close the door; check the microswitch and the delay.
dEF
Defrost
Defrost in progress (shown with d.dL = Lb). Defrost cycle active. Not a fault.
PdF
Defrost
Defrost finished, cooling recovery (with d.dL = Lb). After defrost the temperature has not yet returned to the control value. Not a fault; if it goes on too long, check the evaporator.

NTC 10 kΩ probes from our store

If your unit uses an NTC 10 kΩ probe, these work as replacements. Before buying, check the probe type of your model in its manual (NTC, PTC, Pt1000…).

Controllers of this family in our store

If the fault is internal (memory or clock) and persists, the usual fix is to replace the controller.

Other Osaka families

Consult a technician

Tell us about your case and we will reply. We will include the model, the code and this information.