All the alarm codes that Osaka F-1 / F-10 / F-30 can show (models: F-1, F-10, F-30, Pack F-10 + F-30), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.
Search all families · Is it a drive or a soft starter? Drive and soft starter fault codes
All alarm codes of Osaka F-1 / F-10 / F-30
Models: F-1, F-10, F-30, Pack F-10 + F-30. Official source: Manufacturer manual (osakasolutions.com)
| Code | Meaning | Likely cause | What to check |
|---|---|---|---|
| E1 / -E1 Probe |
Probe Pr1 error (E: probe open; -E: short-circuited). | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. |
| E2 / -E2 Probe |
Probe Pr2 error (E: probe open; -E: short-circuited). | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. |
| E3 / -E3 Probe |
Probe Pr3 error (E: probe open; -E: short-circuited). | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. |
| EPr Memory / internal data |
Possible EEPROM memory fault. | Internal error in the parameter memory. | Press the SET key or switch the unit off and on; if it persists, replace the controller. |
| Err Memory / internal data · Locks the unit |
Serious memory error (irreversible). | Fatal failure of the controller memory. | Replace the controller or send it for repair. |
| od Other |
Start-up delay after power-on in progress. | This is the normal delay after switching on the power. | Not a fault: wait for it to finish. |
| Ln Other |
Keypad locked. | The keypad is locked by a parameter or automatically. | Unlock the keypad as described in the manual. |
| Hi High temperature |
Maximum temperature alarm in progress. | The temperature exceeds the programmed maximum limit. | Check the door, defrost, thermal load and the A.HA limit. |
| Lo Low temperature |
Minimum temperature alarm in progress. | The temperature is below the programmed minimum limit. | Check the setpoint, the compressor contact and the A.LA limit. |
| AL Other |
Digital input alarm in progress. | The digital input configured as an external alarm has been activated. | Check the external equipment and the input configuration (i.Fi). |
| oP Door |
Door open alarm. | The door input has been active for longer than the configured time. | Close the door; check the microswitch and the delay. |
| dEF Defrost |
Defrost in progress (shown with d.dL = Lb). | Defrost cycle active. | Not a fault. |
| PdF Defrost |
Defrost finished, cooling recovery (with d.dL = Lb). | After defrost the temperature has not yet returned to the control value. | Not a fault; if it goes on too long, check the evaporator. |
NTC 10 kΩ probes from our store
If your unit uses an NTC 10 kΩ probe, these work as replacements. Before buying, check the probe type of your model in its manual (NTC, PTC, Pt1000…).
Controllers of this family in our store
If the fault is internal (memory or clock) and persists, the usual fix is to replace the controller.