All the fault codes that WEG CFW500 can show (models: CFW500A01P6B2, CFW500B04P0S2, CFW500C10P0T4, CFW500), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.

Search all families · Is it a refrigeration controller? Refrigeration controller alarm codes

Important: this information is for guidance only and comes from each manufacturer's manual; your particular unit may behave differently, so always check the manual for your exact model. Before resetting, find out and correct the cause of the fault. Work on a drive or a soft starter must only be carried out by qualified persons, with the supply switched off and the DC bus discharged (wait the time stated by the manufacturer). Electrosuministros.es accepts no liability for how this information is used.

All fault codes of WEG CFW500

Models: CFW500A01P6B2, CFW500B04P0S2, CFW500C10P0T4, CFW500. Official source: Manufacturer manual (weg.net)

CodeMeaningLikely causeWhat to check
F0021
Undervoltage · Locks the unit
DC bus undervoltage. Incorrect or low supply voltage, input phase fault, precharge circuit fault. Check the voltage against the nameplate and P0296, the input phases and the precharge.
F0022
Overvoltage · Locks the unit · Braking resistor
DC bus overvoltage. High supply voltage, high inertia or short deceleration ramp. Check the voltage and P0296; lengthen the ramp and use rheostatic braking.
F0031
Communication · Locks the unit
Communication fault with the plug-in module. Plug-in module damaged or poorly connected. Check the module connection; replace it if damaged.
F0033
Parameters · Locks the unit
Autotuning fault (stator resistance). The P0409 value does not match the power, motor incorrectly connected or unsuitable motor power. Check the motor terminal box and repeat the autotuning.
F0048
Overload · Locks the unit
Overload in the IGBT power stage. Output overcurrent (>2xInom). Check the motor, cable and load.
F0051
Temperature · Locks the unit · Cooling fan
IGBT overtemperature. Hot environment (>50 °C), blocked fan or dirty heatsink. Check the ambient temperature and the fan, and clean the heatsink.
F0068
Motor · Locks the unit · Motor
Motor overtemperature (dedicated PTC input). Shaft overload, high duty cycle, hot environment or poor PTC contact. Check the motor and the connection of the triple PTC.
F0070
Overcurrent · Locks the unit
Overcurrent or short circuit at the output, DC bus or braking resistor. Phase-to-phase short circuit, short-circuited braking resistor, damaged IGBT module, short ramp or starting with the motor turning. Disconnect the motor and test; check the wiring, the resistor and the ramps; if it trips without the motor, the drive is damaged.
F0072
Overload · Locks the unit · Motor
Motor overload (60 s at 1.5 Inom). P0156 to P0158 set low compared with the actual current, or an overload on the shaft. Check the overload settings and the mechanical load.
F0074
Earth fault · Locks the unit · Motor
Earth fault (earth overcurrent). Earth short circuit on one or more phases or a cable with high capacitance. Check the insulation of the motor and cable.
F0076
Phase · Locks the unit
Motor connection error. Phase loss, unbalanced currents or motor disconnected. Check the motor wiring and connections.
F0078
Motor · Locks the unit · Motor
Motor overtemperature (AIx or DIx input). Shaft overload, high duty cycle or a probe with poor contact. Check the motor and the probe connection.
F0080
Hardware · Locks the unit · The drive or soft starter itself
CPU fault (watchdog). Electrical noise or firmware fault. Check the shielding and the earthing; if it persists, contact WEG.
F0084
Hardware · Locks the unit · The drive or soft starter itself
Self-diagnosis fault. Poor contact between the control board and the power board, or incompatible hardware. Check the internal connections; if it persists, contact WEG.
F0091
External fault · Locks the unit
External fault via DIx input. Inputs DI1 to DI8 open or with poor contact. Check the input wiring and the external equipment.
F0150
Motor · Locks the unit
Motor overspeed. Incorrect P0161/P0162 settings or a crane-type load. Check the speed settings and the load.
F0179
Hardware · Locks the unit · Cooling fan
Internal fan below speed. Internal fan fault. Check and replace the fan.
F0700
Communication · Locks the unit
No communication with the remote HMI. HMI cable or interface problem. Check the HMI cable and interface.

If the unit has to be replaced

We do not have this drive or soft starter in the online catalogue. This tool suggests a drive or a soft starter based on your motor power; you can also contact us.

Contactors and protection for motors and heating elements

Contact us and we will advise you