All the fault codes that WEG CFW500 can show (models: CFW500A01P6B2, CFW500B04P0S2, CFW500C10P0T4, CFW500), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.
Search all families · Is it a refrigeration controller? Refrigeration controller alarm codes
Important: this information is for guidance only and comes from each manufacturer's manual; your particular unit may behave differently, so always check the manual for your exact model. Before resetting, find out and correct the cause of the fault. Work on a drive or a soft starter must only be carried out by qualified persons, with the supply switched off and the DC bus discharged (wait the time stated by the manufacturer). Electrosuministros.es accepts no liability for how this information is used.
All fault codes of WEG CFW500
Models: CFW500A01P6B2, CFW500B04P0S2, CFW500C10P0T4, CFW500. Official source: Manufacturer manual (weg.net)
| Code | Meaning | Likely cause | What to check |
|---|---|---|---|
| F0021 Undervoltage · Locks the unit |
DC bus undervoltage. | Incorrect or low supply voltage, input phase fault, precharge circuit fault. | Check the voltage against the nameplate and P0296, the input phases and the precharge. |
| F0022 Overvoltage · Locks the unit · Braking resistor |
DC bus overvoltage. | High supply voltage, high inertia or short deceleration ramp. | Check the voltage and P0296; lengthen the ramp and use rheostatic braking. |
| F0031 Communication · Locks the unit |
Communication fault with the plug-in module. | Plug-in module damaged or poorly connected. | Check the module connection; replace it if damaged. |
| F0033 Parameters · Locks the unit |
Autotuning fault (stator resistance). | The P0409 value does not match the power, motor incorrectly connected or unsuitable motor power. | Check the motor terminal box and repeat the autotuning. |
| F0048 Overload · Locks the unit |
Overload in the IGBT power stage. | Output overcurrent (>2xInom). | Check the motor, cable and load. |
| F0051 Temperature · Locks the unit · Cooling fan |
IGBT overtemperature. | Hot environment (>50 °C), blocked fan or dirty heatsink. | Check the ambient temperature and the fan, and clean the heatsink. |
| F0068 Motor · Locks the unit · Motor |
Motor overtemperature (dedicated PTC input). | Shaft overload, high duty cycle, hot environment or poor PTC contact. | Check the motor and the connection of the triple PTC. |
| F0070 Overcurrent · Locks the unit |
Overcurrent or short circuit at the output, DC bus or braking resistor. | Phase-to-phase short circuit, short-circuited braking resistor, damaged IGBT module, short ramp or starting with the motor turning. | Disconnect the motor and test; check the wiring, the resistor and the ramps; if it trips without the motor, the drive is damaged. |
| F0072 Overload · Locks the unit · Motor |
Motor overload (60 s at 1.5 Inom). | P0156 to P0158 set low compared with the actual current, or an overload on the shaft. | Check the overload settings and the mechanical load. |
| F0074 Earth fault · Locks the unit · Motor |
Earth fault (earth overcurrent). | Earth short circuit on one or more phases or a cable with high capacitance. | Check the insulation of the motor and cable. |
| F0076 Phase · Locks the unit |
Motor connection error. | Phase loss, unbalanced currents or motor disconnected. | Check the motor wiring and connections. |
| F0078 Motor · Locks the unit · Motor |
Motor overtemperature (AIx or DIx input). | Shaft overload, high duty cycle or a probe with poor contact. | Check the motor and the probe connection. |
| F0080 Hardware · Locks the unit · The drive or soft starter itself |
CPU fault (watchdog). | Electrical noise or firmware fault. | Check the shielding and the earthing; if it persists, contact WEG. |
| F0084 Hardware · Locks the unit · The drive or soft starter itself |
Self-diagnosis fault. | Poor contact between the control board and the power board, or incompatible hardware. | Check the internal connections; if it persists, contact WEG. |
| F0091 External fault · Locks the unit |
External fault via DIx input. | Inputs DI1 to DI8 open or with poor contact. | Check the input wiring and the external equipment. |
| F0150 Motor · Locks the unit |
Motor overspeed. | Incorrect P0161/P0162 settings or a crane-type load. | Check the speed settings and the load. |
| F0179 Hardware · Locks the unit · Cooling fan |
Internal fan below speed. | Internal fan fault. | Check and replace the fan. |
| F0700 Communication · Locks the unit |
No communication with the remote HMI. | HMI cable or interface problem. | Check the HMI cable and interface. |