All the fault codes that WEG SSW-07 can show (models: SSW070016T5SZ, SSW070061T5SZ, SSW-07), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.

Search all families · Is it a refrigeration controller? Refrigeration controller alarm codes

Important: this information is for guidance only and comes from each manufacturer's manual; your particular unit may behave differently, so always check the manual for your exact model. Before resetting, find out and correct the cause of the fault. Work on a drive or a soft starter must only be carried out by qualified persons, with the supply switched off and the DC bus discharged (wait the time stated by the manufacturer). Electrosuministros.es accepts no liability for how this information is used.

All fault codes of WEG SSW-07

Models: SSW070016T5SZ, SSW070061T5SZ, SSW-07. Official source: Manufacturer manual (static.weg.net)

CodeMeaningLikely causeWhat to check
E03
Phase · Locks the unit
Phase loss or undercurrent. There is no voltage on R/S/T or the motor is disconnected; while running, the current falls below the programmed value (input or output phase). Check the mains, fuses, input contactor, motor connection, thyristors or bypass and the motor current trimpot.
E04
Temperature · Locks the unit · Cooling fan
Overtemperature in the power section. Heatsink temperature above the limit or temperature sensor not connected; the SCR time/temperature curve was exceeded. Check the load, the number of consecutive starts, the internal sensor and whether the ventilation kit (45 to 200 A) is needed; wait for it to cool.
E05
Overload · Locks the unit · Motor
Electronic motor overload. The times of the programmed thermal class were exceeded. Check the motor current trimpot, the start sequence, the thermal class and the load; wait for it to cool.
E19
Hardware · Locks the unit · The drive or soft starter itself
Short circuit in the SSW power section. Current above 30% of rated with the motor stopped. Check for a short-circuited thyristor or internal bypass relay, an external short circuit and the analog current reading.
E62
Overload · Locks the unit
Starting time exceeded with current limit. The start exceeds the ramp trimpot time (only with current-limit starting). Check the ramp time, the current limit and whether the rotor is locked.
E63
Motor · Locks the unit · Motor
Locked rotor (stall). Before full voltage the current exceeds twice the motor rated current. Check the ramp time, the blocked shaft and the supply transformer.
E66
Overcurrent · Locks the unit
Overcurrent. At full voltage, the current exceeds 2 times the trimpot value for more than 1 s. Check for a momentary overload or a locked rotor.
E67
Phase · Locks the unit
Incorrect phase sequence. The synchronism sequence does not follow RST. Reverse the phase sequence of the mains or check the motor connection.
E70
Undervoltage · Locks the unit
Undervoltage in the control supply. The control supply is below 93 Vac. Check the contact and the fuse of the electronics supply.
E71
Hardware · Locks the unit · The drive or soft starter itself
Internal bypass relay contact open. Fault in the internal bypass contacts at full voltage. Check the bypass start cables and contacts damaged by overload.
E72
Overcurrent · Locks the unit
Overcurrent before the bypass. Before the bypass closes, the current exceeds the limit for the model. Check the ramp time, that the motor does not exceed the starter current, and a locked rotor.
E75
External fault · Locks the unit
Frequency out of tolerance. The mains frequency is outside 45 to 66 Hz (e.g. generator set). Check the mains frequency.
E77
Hardware · Locks the unit · The drive or soft starter itself
Bypass contact closed or SCR short-circuited. No voltage difference between input and output is detected when the motor stops. Check the bypass cables, welded contacts, a short-circuited thyristor and external short circuits.

If the unit has to be replaced

We do not have this drive or soft starter in the online catalogue. This tool suggests a drive or a soft starter based on your motor power; you can also contact us.

Contactors and protection for motors and heating elements

Contact us and we will advise you

Other WEG families

  • CFW500 CFW500A01P6B2, CFW500B04P0S2, CFW500C10P0T4, CFW500 · 18 codes
  • SSW900 SSW900, SSW900-A, SSW900-B, SSW900-C · 49 codes
Consult a technician

Tell us about your case and we will reply. We will include the model, the code and this information.