All the fault codes that WEG SSW-07 can show (models: SSW070016T5SZ, SSW070061T5SZ, SSW-07), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.
Search all families · Is it a refrigeration controller? Refrigeration controller alarm codes
Important: this information is for guidance only and comes from each manufacturer's manual; your particular unit may behave differently, so always check the manual for your exact model. Before resetting, find out and correct the cause of the fault. Work on a drive or a soft starter must only be carried out by qualified persons, with the supply switched off and the DC bus discharged (wait the time stated by the manufacturer). Electrosuministros.es accepts no liability for how this information is used.
All fault codes of WEG SSW-07
Models: SSW070016T5SZ, SSW070061T5SZ, SSW-07. Official source: Manufacturer manual (static.weg.net)
| Code | Meaning | Likely cause | What to check |
|---|---|---|---|
| E03 Phase · Locks the unit |
Phase loss or undercurrent. | There is no voltage on R/S/T or the motor is disconnected; while running, the current falls below the programmed value (input or output phase). | Check the mains, fuses, input contactor, motor connection, thyristors or bypass and the motor current trimpot. |
| E04 Temperature · Locks the unit · Cooling fan |
Overtemperature in the power section. | Heatsink temperature above the limit or temperature sensor not connected; the SCR time/temperature curve was exceeded. | Check the load, the number of consecutive starts, the internal sensor and whether the ventilation kit (45 to 200 A) is needed; wait for it to cool. |
| E05 Overload · Locks the unit · Motor |
Electronic motor overload. | The times of the programmed thermal class were exceeded. | Check the motor current trimpot, the start sequence, the thermal class and the load; wait for it to cool. |
| E19 Hardware · Locks the unit · The drive or soft starter itself |
Short circuit in the SSW power section. | Current above 30% of rated with the motor stopped. | Check for a short-circuited thyristor or internal bypass relay, an external short circuit and the analog current reading. |
| E62 Overload · Locks the unit |
Starting time exceeded with current limit. | The start exceeds the ramp trimpot time (only with current-limit starting). | Check the ramp time, the current limit and whether the rotor is locked. |
| E63 Motor · Locks the unit · Motor |
Locked rotor (stall). | Before full voltage the current exceeds twice the motor rated current. | Check the ramp time, the blocked shaft and the supply transformer. |
| E66 Overcurrent · Locks the unit |
Overcurrent. | At full voltage, the current exceeds 2 times the trimpot value for more than 1 s. | Check for a momentary overload or a locked rotor. |
| E67 Phase · Locks the unit |
Incorrect phase sequence. | The synchronism sequence does not follow RST. | Reverse the phase sequence of the mains or check the motor connection. |
| E70 Undervoltage · Locks the unit |
Undervoltage in the control supply. | The control supply is below 93 Vac. | Check the contact and the fuse of the electronics supply. |
| E71 Hardware · Locks the unit · The drive or soft starter itself |
Internal bypass relay contact open. | Fault in the internal bypass contacts at full voltage. | Check the bypass start cables and contacts damaged by overload. |
| E72 Overcurrent · Locks the unit |
Overcurrent before the bypass. | Before the bypass closes, the current exceeds the limit for the model. | Check the ramp time, that the motor does not exceed the starter current, and a locked rotor. |
| E75 External fault · Locks the unit |
Frequency out of tolerance. | The mains frequency is outside 45 to 66 Hz (e.g. generator set). | Check the mains frequency. |
| E77 Hardware · Locks the unit · The drive or soft starter itself |
Bypass contact closed or SCR short-circuited. | No voltage difference between input and output is detected when the motor stops. | Check the bypass cables, welded contacts, a short-circuited thyristor and external short circuits. |