All the fault codes that WEG SSW900 can show (models: SSW900, SSW900-A, SSW900-B, SSW900-C), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.
Search all families · Is it a refrigeration controller? Refrigeration controller alarm codes
Important: this information is for guidance only and comes from each manufacturer's manual; your particular unit may behave differently, so always check the manual for your exact model. Before resetting, find out and correct the cause of the fault. Work on a drive or a soft starter must only be carried out by qualified persons, with the supply switched off and the DC bus discharged (wait the time stated by the manufacturer). Electrosuministros.es accepts no liability for how this information is used.
All fault codes of WEG SSW900
Models: SSW900, SSW900-A, SSW900-B, SSW900-C. Official source: Manufacturer manual (static.weg.net)
| Code | Meaning | Likely cause | What to check |
|---|---|---|---|
| F001 Phase · Locks the unit |
Motor voltage imbalance. | The line voltage imbalance exceeds the programmed value (C5.1.3.2) for the programmed time. | Check the balance of the mains and for loss of a supply phase. |
| F002 Undervoltage · Locks the unit |
Supply undervoltage. | Mains voltage below the programmed value (C5.1.1.2) for the programmed time; a dip on starting, a small transformer or phase loss. | Check the mains, the input transformer and the phases. |
| F003 Phase · Locks the unit |
Phase loss at start-up. | A line voltage is below the permitted value when starting begins, or the PLL was not initialised because of a programming error. | Check the input phases, the motor voltage (C2.1), the input contactor, the fuses and the connections. |
| F005 Overload · Locks the unit · Motor |
Motor thermal overload. | The thermal class curve time was exceeded (excessive starts, a class that is too low or little cooling time between starts). | Check the programmed thermal class (C5.9), the number of starts and the cooling time. |
| F010 Hardware · Locks the unit · The drive or soft starter itself |
CCI fault (internal communication between boards). | Fault in the communication between the control interface board and the motor control board (reserved). | Contact WEG service. |
| F015 Phase · Locks the unit |
Motor not connected. | A current synchronisation pulse is missing at start-up. | Check the motor connections and whether there is a short-circuited SCR or bypass. |
| F016 Overvoltage · Locks the unit |
Supply overvoltage. | Mains voltage above the programmed value (C5.1.2.2) for the programmed time. | Check the transformer tap and the mains. |
| F018 Phase · Locks the unit |
Incorrect connection to the motor. | The output voltage is incorrect with the motor disabled. | Check the motor connections and the inside-delta programming (C9.2.1). |
| F019 Hardware · Locks the unit · The drive or soft starter itself |
Power short circuit with the motor stopped. | A three-phase current exceeds the SSW rated current by 25% for more than 50 ms. | Check for a short-circuited SCR or bypass and the current measurement circuit. |
| F020 Overcurrent · Locks the unit |
Power short circuit with the motor running. | A current exceeds five times the rated current for more than 0.75 ms. | Check for a short circuit in the SSW power section, the cables, the motor, or a locked rotor. |
| F032 Temperature · Locks the unit · Motor |
Motor overtemperature on DI6 (PTC). | Input DI6, programmed for PTC, has been activated. | Check the load, the number of starts, the ambient temperature and the PTC wiring. |
| F040 Hardware · Locks the unit · The drive or soft starter itself |
CCI-CCM serial communication fault. | Communication between the interface board and the motor board is interrupted; to clear it you have to switch off and on. | Check for electrical noise, the earthing of the electronics supply and the control boards. |
| F042 Hardware · Locks the unit · The drive or soft starter itself |
CPU error (watchdog). | Microcontroller watchdog fault, due to electrical noise or poor earthing. | Check the electrical noise and the earthing of the electronics supply. |
| F051 Temperature · Locks the unit |
SCR undertemperature. | The SCR heatsink temperature is below the permitted value (-20 °C). | Check the ambient temperature and the heatsink NTC cables. |
| F054 Temperature · Locks the unit · Cooling fan |
SCR overtemperature. | The SCR heatsink temperature exceeds the permitted value. | Check the start cycle, the fan, the ambient temperature and the mounting of the SCRs. |
| F057 Hardware · Locks the unit · The drive or soft starter itself |
SCR fault on arm R-U. | No SCR fires for more than 50 ms. | Check the SCR gate, the firing circuit and the firing cables. |
| F058 Hardware · Locks the unit · The drive or soft starter itself |
SCR fault on arm S-V. | No SCR fires for more than 50 ms. | Check the SCR gate, the firing circuit and the firing cables. |
| F059 Hardware · Locks the unit · The drive or soft starter itself |
SCR fault on arm T-W. | No SCR fires for more than 50 ms. | Check the SCR gate, the firing circuit and the firing cables. |
| F061 Parameters · Locks the unit |
Insufficient time between starts. | A start command was received before the minimum interval between starts (C5.7.3). | Respect the minimum interval or check its programming. |
| F062 Overload · Locks the unit |
Starting time exceeded. | The maximum starting time (C1.3) was exceeded with current limit, current ramp or torque control. | Check the time C1.3, the current (C1.7) and torque limits, and whether the rotor is locked. |
| F063 Motor · Locks the unit · Motor |
Locked rotor. | At the end of the ramp the current does not fall below 2 times the rated current before the bypass closes. | Check the motor rated current (C2.2), the time C1.3, the transformer and that the rotor is not locked. |
| F064 Overload · Locks the unit · The drive or soft starter itself |
SCR overload. | The limits of the SCR protection time x temperature curve were exceeded. | Check the start cycles, the current and starting time, the time between starts and the fan. |
| F065 Overload · Locks the unit |
Motor undercurrent. | The current falls below the programmed value (C5.2.1.2) for the programmed time (e.g. pump running dry). | Check the load and the protection programming. |
| F066 Overcurrent · Locks the unit |
Motor overcurrent. | The current exceeds the programmed value (C5.2.2.2) for the programmed time. | Check for a momentary overload of the load or a locked rotor. |
| F067 Phase · Locks the unit |
RST/123 phase reversal. | The synchronism signals do not follow the sequence R/1L1, S/3L2, T/5L3. | Check the phase sequence of the line. |
| F068 Phase · Locks the unit |
RTS/132 phase reversal. | The synchronism signals do not follow the sequence R/1L1, T/5L3, S/3L2. | Check the phase sequence of the line. |
| F069 Undervoltage · Locks the unit |
Incorrect control supply voltage. | The control board supply is out of specification. | Check the voltage and the contacts of the control supply. |
| F070 Undervoltage · Locks the unit |
Control circuit undervoltage. | The control board supply is below 93.5 Vac. | Check the phase, the contacts and the fuse of the control supply (5 x 20 mm, 2 A). |
| F071 Hardware · Locks the unit · The drive or soft starter itself |
Bypass contact open / not closed. | A fault is detected in the bypass contacts at full voltage after starting. | Check the bypass control cables, the board and the contactor coil, and contacts damaged by overload. |
| F072 Overcurrent · Locks the unit |
Overcurrent before the bypass. | At the end of the ramp the current does not fall below 2 times the SSW rated current before the bypass closes. | Check the rated current (C2.2), the acceleration ramp, that the motor does not exceed the permitted current, and a locked rotor. |
| F074 Phase · Locks the unit |
Motor current imbalance. | The difference between phase currents exceeds the programmed value (C5.2.3.2). | Check for a voltage drop on one phase, phase loss, the transformer, fuses and contacts. |
| F075 External fault · Locks the unit |
Frequency out of range. | The mains frequency is outside 50/60 Hz ±10% for more than 0.5 s with the motor on. | Check whether it is supplied by a generator set that cannot handle the load or the start. |
| F076 Phase · Locks the unit |
Undercurrent in the bypass. | At the end of the ramp, before the bypass closes, the current is below 0.1 times the rated current. | Check the line voltage, an SCR and the rated current programming (C9.1.1). |
| F077 Hardware · Locks the unit · The drive or soft starter itself |
Bypass contact closed / not open. | The bypass does not open: short-circuited cables, welded contacts, short-circuited SCR or external bypass. | Check the cables, contacts, SCRs and external short circuits. |
| F078 Overload · Locks the unit |
Insufficient motor torque. | The undertorque exceeds the programmed value for the programmed time (e.g. pump running dry). | Check the load and the programming. |
| F079 Overload · Locks the unit |
Motor overtorque. | The overtorque exceeds the programmed value for the programmed time. | Check for a momentary overload or a locked rotor. |
| F080 Overload · Locks the unit |
Insufficient motor power. | The underpower exceeds the programmed value for the programmed time. | Check the load (e.g. pump running dry) and the programming. |
| F081 Overload · Locks the unit |
Motor overpower. | The overpower exceeds the programmed value for the programmed time. | Check for a momentary overload or a locked rotor. |
| F082 Hardware · Locks the unit |
Slot 1 fault: incompatible accessory. | The SLOT1 accessory is not compatible with the firmware. | Update the firmware or check the accessory. |
| F083 Hardware · Locks the unit |
Slot 2 fault: incompatible accessory. | The SLOT2 accessory is not compatible with the firmware. | Update the firmware or check the accessory. |
| F084 Hardware · Locks the unit · The drive or soft starter itself |
Self-diagnosis fault. | Problem detected during operating system initialisation (the STATUS LED flashes red with the number). | Check the firmware package and the control board; contact WEG. |
| F085 Hardware · Locks the unit |
Slot 1 = Slot 2: identical accessories. | Two identical accessories are installed. | Leave only one accessory of each type. |
| F086 Hardware · Locks the unit |
Slot 1 fault: required accessory not installed. | The required SLOT1 accessory is not installed or was removed. | Install it or check the C9.3.1 programming. |
| F087 Hardware · Locks the unit |
Slot 2 fault: required accessory not installed. | The required SLOT2 accessory is not installed or was removed. | Install it or check the C9.3.2 programming. |
| F088 Hardware · Locks the unit |
Accessory connection fault in slot 1. | The SLOT1 accessory was removed or is faulty. | Check the accessory. |
| F089 Hardware · Locks the unit |
Accessory connection fault in slot 2. | The SLOT2 accessory was removed or is faulty. | Check the accessory. |
| A090 External fault |
External alarm (DI). | A digital input programmed as an external alarm opens. | Check for open wiring on DI1 to DI6. |
| F091 External fault · Locks the unit |
External fault (DI). | A digital input programmed as an external fault opens. | Check for open wiring on DI1 to DI6. |
| F099 Hardware · Locks the unit · The drive or soft starter itself |
Invalid current offset. | The reading of a current input is outside the 2.5 V ±3% range. | Check the current transformer cables, a short-circuited SCR or bypass and the control board. |