All the alarm codes that Eliwell EWNext can show (models: EWNext 961 O/B, EWNext 974 O/B, EWNext Optimized NA), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.

Search all families · Is it a drive or a soft starter? Drive and soft starter fault codes

Important: this information is for guidance only and comes from each manufacturer's manual; your particular unit may behave differently, so always check the manual for your exact model. Any inspection or repair must be carried out by a qualified professional. Electrosuministros.es accepts no liability for how it is used.

All alarm codes of Eliwell EWNext

Models: EWNext 961 O/B, EWNext 974 O/B, EWNext Optimized NA. Official source: Manufacturer manual (eliwell.com)

CodeMeaningLikely causeWhat to check
E1
Probe
Pb1 probe error (cold room). Probe disconnected, short-circuited or out of range, or cable damaged. Check the configured probe type and the wiring, and measure the probe; replace it if damaged. While it lasts, the compressor runs according to Ont/OFt.
E2
Probe
Pb2 probe error (only models that manage it). Probe disconnected, short-circuited or out of range, or cable damaged. Check the configured probe type and the wiring, and measure the probe; replace it if damaged. Defrost ends by time (dEt).
AH1
High temperature
High temperature alarm on the cold room probe (Pb1). The temperature has exceeded the maximum limit for longer than the programmed delay. Wait for it to come down; check the door, defrost, fan, cold room load and the alarm limit.
AL1
Low temperature
Low temperature alarm on the cold room probe (Pb1). The temperature has dropped below the minimum limit for longer than the programmed delay. Check the setpoint, the differential, the compressor contact and the alarm limit.
EA
Other
External alarm from a digital input. The digital input configured as an external alarm has been activated. Check the equipment or external contact connected to the input and the digital input configuration.
oPd
Door · Locks the unit
Door open alarm. The door input has been active for longer than the configured delay. Close the door and check the microswitch, its wiring and the alarm delay.
Ad2
Defrost
Defrost ended by maximum time, not by temperature. The end-of-defrost temperature (evaporator probe) was not reached within the maximum time. Check the evaporator probe, the defrost heaters and the duration and end temperature parameters.
rFA
Other
Lack of refrigerant alarm. With the compressor running, the temperature does not change within the rFt interval. Check the refrigerant charge, leaks and the condition of the compressor; switch off and on (disabled if rFt=0).

NTC 10 kΩ probes from our store

If your unit uses an NTC 10 kΩ probe, these work as replacements. Before buying, check the probe type of your model in its manual (NTC, PTC, Pt1000…).

Other Eliwell families

  • IDNext IDNext 902 P, IDNext 961 P, IDNext 971 P/B, IDNext 974 P/B, IDNext 978 P/B, IDNext 978 P/C · 13 codes
  • nEW / IDS (961-971-974) nEW 961, nEW 971, nEW 971 SPDT, nEW 974, IDS 961, IDS 974 · 7 codes
  • ID 985 ID985/E LXC, ID985 LX HG, ID985/S/E/C/K LX (TOP), ID985/S/E/C/K MB · 13 codes
  • EWRC NT (Coldface) EWRC 300 NT, EWRC 500 NT, EWRC 500 NT 4D, EWRC 500 NT 4D W/B, EWRC 5000 NT · 7 codes
  • ID Plus / EWPlus (antiguos) ID Plus 902, ID Plus 961, ID Plus 971, ID Plus 974, ID Plus 961-974 HC, EWPlus 974 EL, ID 974 · 11 codes
Consult a technician

Tell us about your case and we will reply. We will include the model, the code and this information.