All the alarm codes that Eliwell IDNext can show (models: IDNext 902 P, IDNext 961 P, IDNext 971 P/B, IDNext 974 P/B, IDNext 978 P/B, IDNext 978 P/C), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.
Search all families · Is it a drive or a soft starter? Drive and soft starter fault codes
All alarm codes of Eliwell IDNext
Models: IDNext 902 P, IDNext 961 P, IDNext 971 P/B, IDNext 974 P/B, IDNext 978 P/B, IDNext 978 P/C. Official source: Manufacturer manual (eliwell.com)
| Code | Meaning | Likely cause | What to check |
|---|---|---|---|
| E1 Probe |
Pb1 probe error (cold room). | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. While it lasts, the compressor runs according to Ont/OFt and the maximum and minimum alarms are disabled. |
| E2 Probe |
Pb2 probe error (evaporator, 97x models only). | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. Defrost ends by time (dEt). |
| E3 Probe |
Pb3 probe error. | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. |
| AH1 High temperature |
High temperature alarm on the cold room probe (Pb1). | The temperature has exceeded the maximum limit for longer than the programmed delay. | Wait for it to come down; check the door, defrost, fan, cold room load and the alarm limit. |
| AL1 Low temperature |
Low temperature alarm on the cold room probe (Pb1). | The temperature has dropped below the minimum limit for longer than the programmed delay. | Check the setpoint, the differential, the compressor contact and the alarm limit. |
| EA Other |
External alarm from a digital input. | The digital input configured as an external alarm has been activated. | Check the equipment or external contact connected to the input and the digital input configuration. |
| Opd Door · Locks the unit |
Door open alarm. | The door input has been active for longer than the configured delay. | Close the door and check the microswitch, its wiring and the alarm delay. |
| Ad2 Defrost |
Defrost ended by maximum time, not by temperature. | The end-of-defrost temperature (evaporator probe) was not reached within the maximum time. | Check the evaporator probe, the defrost heaters and the duration and end temperature parameters. |
| COH High temperature · Locks the unit |
Overheating alarm (probe 3 temperature above SA3). | Probe 3 has exceeded the SA3 value. | Check the condenser (cleaning, fan), probe 3 and the SA3 threshold. |
| E10 Clock |
Clock alarm (faulty clock or low battery). | The internal clock is not set or the battery is flat. | Set the date and time; if it persists, replace the controller (flat battery). |
| rFA Other |
Lack of refrigerant alarm. | With the compressor running, the temperature does not change within the rFt interval. | Check the refrigerant charge, leaks and the condition of the compressor; switch off and on (disabled if rFt=0). |
| nPA Pressure switch · Locks the unit |
Pressure switch activation warning (still below the maximum number). | The external pressure switch has tripped fewer times than the maximum allowed (PEn). | Check the pressures, the condenser fan and the pressure switch. |
| PAL Pressure switch · Locks the unit |
Pressure switch alarm locked after repeated trips. | The maximum number of pressure switch trips in the configured time was reached. | Check the pressures, the condenser and the pressure switch; restart the unit or reset it from the functions menu (rAP). |
NTC 10 kΩ probes from our store
If your unit uses an NTC 10 kΩ probe, these work as replacements. Before buying, check the probe type of your model in its manual (NTC, PTC, Pt1000…).
Controllers of this family in our store
If the fault is internal (memory or clock) and persists, the usual fix is to replace the controller.
Other Eliwell families
- EWNext EWNext 961 O/B, EWNext 974 O/B, EWNext Optimized NA · 8 codes
- nEW / IDS (961-971-974) nEW 961, nEW 971, nEW 971 SPDT, nEW 974, IDS 961, IDS 974 · 7 codes
- ID 985 ID985/E LXC, ID985 LX HG, ID985/S/E/C/K LX (TOP), ID985/S/E/C/K MB · 13 codes
- EWRC NT (Coldface) EWRC 300 NT, EWRC 500 NT, EWRC 500 NT 4D, EWRC 500 NT 4D W/B, EWRC 5000 NT · 7 codes
- ID Plus / EWPlus (antiguos) ID Plus 902, ID Plus 961, ID Plus 971, ID Plus 974, ID Plus 961-974 HC, EWPlus 974 EL, ID 974 · 11 codes