All the alarm codes that Eliwell nEW / IDS (961-971-974) can show (models: nEW 961, nEW 971, nEW 971 SPDT, nEW 974, IDS 961, IDS 974), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.
Search all families · Is it a drive or a soft starter? Drive and soft starter fault codes
Important: this information is for guidance only and comes from each manufacturer's manual; your particular unit may behave differently, so always check the manual for your exact model. Any inspection or repair must be carried out by a qualified professional. Electrosuministros.es accepts no liability for how it is used.
All alarm codes of Eliwell nEW / IDS (961-971-974)
Models: nEW 961, nEW 971, nEW 971 SPDT, nEW 974, IDS 961, IDS 974. Official source: Manufacturer manual (eliwell.com)
| Code | Meaning | Likely cause | What to check |
|---|---|---|---|
| E1 Probe |
Pb1 probe error (cold room). | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. The compressor runs according to P0/P1 and the maximum and minimum alarms are cancelled. |
| E2 Probe |
Pb2 probe error (defrost, 971/974 only). | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. Defrost ends by time (d3) and the evaporator fans are switched off. |
| Ht High temperature |
High temperature alarm on the cold room probe (Pb1). | The temperature has exceeded the maximum limit for longer than the programmed delay. | Wait for it to come down; check the door, defrost, fan, cold room load and the alarm limit. |
| Lt Low temperature |
Low temperature alarm on the cold room probe (Pb1). | The temperature has dropped below the minimum limit for longer than the programmed delay. | Check the setpoint, the differential, the compressor contact and the alarm limit. |
| EA Other |
External alarm from a digital input. | The digital input configured as an external alarm has been activated. | Check the equipment or external contact connected to the input and the digital input configuration. |
| OP Door |
Door open alarm. | The door input has been active for longer than the configured delay. | Close the door and check the microswitch, its wiring and the alarm delay. |
| ES Other |
Energy saving active (reduced setpoint). | Activated by a digital input or by a key. | Not a fault: check the digital input or the key if it was not expected. |
NTC 10 kΩ probes from our store
If your unit uses an NTC 10 kΩ probe, these work as replacements. Before buying, check the probe type of your model in its manual (NTC, PTC, Pt1000…).
EVCO EVTPN615F200 - NTC 10 kΩ temperature probe, overmoulded IP67, 1.5 m flat cable
Ref. EVTPN615F200
€6.05
View product
NTC probe 6x40 mm PVC 1.5 m - Eliwell NTC 10K temperature probe, IP67, -30/+80 °C
Ref. SN8P0A1500
€8.91
View product
NTC probe 6x40 mm PVC 3 m - Eliwell NTC 10K temperature probe, IP67, -30/+80 °C
Ref. SN8P0A3000
€10.29
View product
Other Eliwell families
- IDNext IDNext 902 P, IDNext 961 P, IDNext 971 P/B, IDNext 974 P/B, IDNext 978 P/B, IDNext 978 P/C · 13 codes
- EWNext EWNext 961 O/B, EWNext 974 O/B, EWNext Optimized NA · 8 codes
- ID 985 ID985/E LXC, ID985 LX HG, ID985/S/E/C/K LX (TOP), ID985/S/E/C/K MB · 13 codes
- EWRC NT (Coldface) EWRC 300 NT, EWRC 500 NT, EWRC 500 NT 4D, EWRC 500 NT 4D W/B, EWRC 5000 NT · 7 codes
- ID Plus / EWPlus (antiguos) ID Plus 902, ID Plus 961, ID Plus 971, ID Plus 974, ID Plus 961-974 HC, EWPlus 974 EL, ID 974 · 11 codes