All the alarm codes that Eliwell ID 985 can show (models: ID985/E LXC, ID985 LX HG, ID985/S/E/C/K LX (TOP), ID985/S/E/C/K MB), with their meaning, likely cause and what to check in each case. If the code on your display is not in the list, search the other families or contact us.
Search all families · Is it a drive or a soft starter? Drive and soft starter fault codes
All alarm codes of Eliwell ID 985
Models: ID985/E LXC, ID985 LX HG, ID985/S/E/C/K LX (TOP), ID985/S/E/C/K MB. Official source: Manufacturer manual (eliwell.com)
| Code | Meaning | Likely cause | What to check |
|---|---|---|---|
| E1 Probe |
Probe 1 error (thermostat). | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. The compressor runs according to Ont/OFt. |
| E2 Probe |
Probe 2 error (evaporator). | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. Defrost ends by time. |
| E3 Probe |
Probe 3 error (display or 2nd evaporator). | Probe disconnected, short-circuited or out of range, or cable damaged. | Check the configured probe type and the wiring, and measure the probe; replace it if damaged. |
| AH1 High temperature |
High temperature alarm on probe 1. | The temperature has exceeded the maximum limit for longer than the programmed delay. | Wait for it to come down; check the door, defrost, fan, cold room load and the alarm limit. |
| AL1 Low temperature |
Low temperature alarm on probe 1. | The temperature has dropped below the minimum limit for longer than the programmed delay. | Check the setpoint, the differential, the compressor contact and the alarm limit. |
| AH3 High temperature |
High temperature alarm on probe 3. | The temperature has exceeded the maximum limit for longer than the programmed delay. | Wait for it to come down; check the door, defrost, fan, cold room load and the alarm limit. |
| AL3 Low temperature |
Low temperature alarm on probe 3. | The temperature has dropped below the minimum limit for longer than the programmed delay. | Check the setpoint, the differential, the compressor contact and the alarm limit. |
| Ad2 Defrost |
Defrost ended by maximum time, not by temperature. | The end-of-defrost temperature (evaporator probe) was not reached within the maximum time. | Check the evaporator probe, the defrost heaters and the duration and end temperature parameters. |
| EA Other · Locks the unit |
External alarm from a digital input. | Digital input active; depending on rLO it can stop the compressor, defrost and fans. | Check the external equipment or contact and the rLO parameter. |
| Opd Door |
Door open alarm. | The door has been open for longer than the tdO delay. | Close the door; check the microswitch and tdO. |
| PA Pressure switch · Locks the unit |
Pressure switch alarm. | The pressure switch has tripped through the digital input. | Check the pressures, the condenser and the pressure switch. |
| E7 Communication |
Master-slave communication failure (no link). | Communication is lost in the master/slave/echo network or there are duplicate addresses. | Check the network wiring, the addresses and the number of slaves in the master. |
| E10 Clock |
Clock battery alarm (models with clock). | Clock battery flat or clock not set. | Set the clock; if it persists, replace the controller. |
NTC 10 kΩ probes from our store
If your unit uses an NTC 10 kΩ probe, these work as replacements. Before buying, check the probe type of your model in its manual (NTC, PTC, Pt1000…).
Controllers of this family in our store
If the fault is internal (memory or clock) and persists, the usual fix is to replace the controller.
Other Eliwell families
- IDNext IDNext 902 P, IDNext 961 P, IDNext 971 P/B, IDNext 974 P/B, IDNext 978 P/B, IDNext 978 P/C · 13 codes
- EWNext EWNext 961 O/B, EWNext 974 O/B, EWNext Optimized NA · 8 codes
- nEW / IDS (961-971-974) nEW 961, nEW 971, nEW 971 SPDT, nEW 974, IDS 961, IDS 974 · 7 codes
- EWRC NT (Coldface) EWRC 300 NT, EWRC 500 NT, EWRC 500 NT 4D, EWRC 500 NT 4D W/B, EWRC 5000 NT · 7 codes
- ID Plus / EWPlus (antiguos) ID Plus 902, ID Plus 961, ID Plus 971, ID Plus 974, ID Plus 961-974 HC, EWPlus 974 EL, ID 974 · 11 codes